Part Ⅰ: 220kV Power Transformer Overview

220kV series oil immersed power transformer adopts the combination of advanced production equipment and lean manufacturing technology, and has the advantages of low loss, low noise, strong ability to resist sudden short circuit and beautiful appearance. The transformer can have the four remote functions of "remote signaling, telemetry, remote adjustment and remote control", and can realize unattended substation through computer remote control.


The transformer structure layout is reasonable. According to the calculation and analysis results, a reasonable insulation structure, wire specifications and magnetic flux density are selected. Perform accurate calculations on various cooling methods, perform thermal calculations on periodic overloads and temporary overloads of windings, and select the most suitable cooling method among cooling methods such as fin air cooling, strong oil air cooling, and strong oil water cooling. Minimize the oil level and winding temperature rise.


220kV 3-phase 2-winding Power Transformer

Product Attributes

Model No.


Application

Power

Coil

Core-type Transformer

Frequency

50/60Hz

Phase

Three

Cooling Method

Oil-immersed Type Transformer

Capacity range:

31500kVA-240000kVA

Operating Ambient Temperature

+40 °C--30 °C

Operating Altitude

≤1000m

Operating Max Wind Speed

≤35m/s

Earthquake acceleration

horizontal acceleration ≤0.3g

vertica I acceleration ≤0.15g

Standard

IEC 60076-1:2000, IEC 60076-2:1993, IEC 60076-3:2000, IEC 60076-5:2006, IEC 60137:2003; ANSI, IEEE, AS, etc.

Supply Ability & Additional Information

Packaging

Seaworthy Packing

Transportation

Ocean

Supply Ability

High

HS Code

85042100

Payment Type

L/C, T/T

Delivery Time

60 Days

Place of Origin

China

Port

China Sea Port

Incoterm

FOB, CFR, CIF

Packaging & Delivery

Selling Units:

Set/Sets

Package Type:

Seaworthy Packing


Part Ⅱ: Product Features

1. High Reliability:

Insulation strength: through the method of finite elements analysis, analyze the interior electric field on different transformer for the purpose that there is no over-centralized area of field density in the interior of transformer for the purpose that there is no over-centralized area of field density in the interior of transformer. At the same time, by the adoption of insulating materials and optimizing electrode shape, make no partial discharge design, and through the effective analysis on transformer wave process, ensure that the effective analysis on transformer wave process, ensure that the transformer can withstand various over-voltages such as, lighting impulse over-voltage.



2. Low power loss and low operation cost

The transformer has relatively low losses through the optimized design, the detailed analysis of leakage magnetic field and the losses distribution. The maintenance cost has been lowered through the Customer-oriented design.



3. Customer-oriented Design

Based on the 3D design method to simulate feeders, operation filed and terminal box arrangement are in full consideration of operating conveniences, which meets the requirements on cost lowering and customization, as well.


Part Ⅲ: Structural Feature

1. Iron Core

The iron core is made of cold rolled, granular-oriented, low-loss and high magnetic conductive silicon steel sheet, which is of multi-step completely tilted structure to reduce the loss and noise.

2. Winding

① HV winding adopts entanglement or inner screened continuous type with phase insulation structure to ensure insulating strength.

② MV/LV windings adopt high strength or adhibit-transpostion conductor, reinforced cooling to reduce the temperature rise and enhance capability of short circuit withstand.


3. Oil Tank

Thee-dimension finite element strength analysis and Pro-E mold is adopted, which have reinforced the mechanical strength.



4. Assembly and routine test

High qualified components to ensure good performances.


Part Ⅳ: Product Main Parameter

31500~360000kVA/220 Two-winding Oil-immersed Transformer with NVTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Impedance Voltage %

No Load Current

%

No Load Losses

kW

On Load Losses

kW

HV

LV

31500

220±2×2.5%

242±2×2.5%

6.3, 6.6, 10.5, 11

YNd11

12~14

0.7

35

135

40000

0.7

41

157

50000

0.65

49

189

63000

0.65

58

220

90000

10.5, 13.8, 11

0.55

77

288

120000

0.55

94

345

150000

11, 13.8, 15.75

0.50

112

405

180000

0.46

128

459

240000

0.42

160

567

300000

15.75, 18

0.38

189

675

360000

0.38

217

774


31500~240000kVA/110 Three-Winding Oil-immersed Transformer with NVTC NVTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

No Load Current

%

Impedance Voltage %

No Load Losses

kW

On Load Losses

kW

HV

MV

LV

Step up

Step down

31500

220±2×2.5%, 242±2×2.5%

69, 121

6.3, 6.6, 10.5, 11, 35, 38.5

YNyn0d11

0.7

HV~MV: 22~24

HV~LV: 12~14

MV~LV: 7~9

HV~MV: 12~14

HV~LV: 22~24

MV~LV: 7~9

40

162

40000

0.63

48

189

50000

0.56

56

225

63000

0.56

66

261

90000

10.5, 11, 13.8, 35, 38.5

0.49

86

351

120000

0.49

106

432

150000

11, 13.8, 15.75, 35, 38.5

0.42

125

513

180000

0.42

142

585

240000

0.35

176

720


31500~240000kVA/220 Oil-immersed Transformer with NVTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Impedance Voltage %

No Load Current

%

No Load Losses

kW

On Load Losses

kW

HV

LV

31500

220±2×2.5%

63, 66, 69

YNd11

12~14

0.89

38

151

40000

0.89

45

176

50000

0.82

53

211

63000

0.82

63

247

90000

0.75

83

323

120000

0.75

102

387

150000

0.68

122

453

180000

0.68

138

513

240000

0.61

171

635


31500~240000kVA/220 Oil-immersed Transformer with NVTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Setp-up set

Step-down set

Short-circuit Impedance%

HV

MV

LV

No Load Current

%

No Load Losses

kW

On Load Losses

kW

No Load Current

%

No Load Losses

kW

On Load Losses

kW

Step-up

Step-down

31500

220±2×2.5%

242±2×2.5%

121

6.6, 10.5, 11, 35, 37, 38.5

YNa0d11

0.57

25

117

22

99

0.5

HV~MV: 12~14

HV~LV: 8~12

MV~LV: 14~18

HV~MV: 8~10

HV~LV: 28~34

MV~LV: 18~24

40000

0.57

29

144

26

121

0.5

50000

0.5

34

170

30

144

0.43

63000

0.5

40

201

36

171

0.43

90000

0.43

50

276

46

234

0.36

120000

10.5, 11, 13.8, 15.75, 18.35, 37, 38.5

0.43

62

340

56

288

0.36

150000

0.36

73

405

66

342

0.33

180000

0.36

84

463

76

387

0.33

240000

0.33

99

595

89

504

0.25


31500~180000kVA/220 Two-winding Oil-immersed Transformer with OLTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Short-circuit

Impedance%

No Load Current

%

No Load Losses

kW

On Load Losses

kW

HV

LV

31500

220±8×1.25%

6.3, 6.6, 10.5, 11, 35, 37, 38.5

YNd11

12~14

0.77

38

135

40000

0.63

45

157

50000

0.56

54

189

63000

0.56

63

220

90000

10.5, 11, 35, 37, 38.5

0.49

80

288

120000

0.49

99

346

150000

0.42

116

405

180000

0.42

135

468


31500~240000kVA/220 Oil-immersed Transformer with OLTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Setp-up set

Capacity Allocation %

Short-circuit Impedance%

HV

MV

LV

No Load Current

%

No Load Losses

kW

On Load Losses

kW

31500

220±8×1.25%

115

6.3, 6.6, 10.5, 11, 35, 37, 38.5

YNa0d11

0.56

25

108

100/100/50

HV~MV: 8~10

HV~LV: 28~34

MV~LV: 18~24

40000

0.56

30

132

50000

0.49

36

157

63000

0.49

42

189

90000

0.42

51

247

120000

10.5, 11, 35, 37, 38.5

0.42

64

308

150000

0.35

73

365

180000

0.35

85

419

240000

0.3

104

540


63000~180000kVA/220 Autotransformer with OLTC (HV neutral is indirect grounding)

Rated Capacity (kVA)

Rated Voltage and Tapping Range

Vector Group

Setp-up set

Capacity Allocation %

Short-circuit Impedance%

HV

MV

LV

No Load Current

%

No Load Losses

kW

On Load Losses

kW

63000

220±8×1.25%

115

6.3, 6.6, 10.5, 11, 35, 37, 38.5

YNa0d11

0.49

42

189

100/100/50

HV~MV: 8~10

HV~LV: 28~34

MV~LV: 18~24

90000

0.42

51

247

120000

0.42

64

308

150000

10.5, 11, 35, 37, 38.5

0.35

85

365

180000

0.35

104

419


Part Ⅳ: Structural Diagram


Part Ⅴ: Quality Warranty


Part Ⅵ: Application


Part Ⅶ: Packaging and Transportation


Before packing the transformer, make a packing plan, and carry out packing according to the design scheme and plan when packing. The packing list corresponds to the materials in the box one to one. Pack the box in two copies, one in the packing box and the other nailed outside the packing box. Important parts and spare parts are packed in wooden boxes, and the box numbers are set in order.

The transformer is transported in bare installation, and the fuel tank is emptied before transport. It is tied to a transport vehicle by a wire rope, and the transport speed does not exceed 15km/h.

The terminal is guaranteed to have large-scale transformer lifting equipment, and the lashing is firm after loading to ensure safe and reliable transportation.


Part Ⅷ: Factory Tour


Part Ⅸ: Service Guarantee

1. To provide all technical information and drawings as per contract promptly. QRE is oblidged to invite client, if neccessory, technical design review.

2. To carry out spot technical service as per client’s schedule, offer guideness for installation and commis-sioning according to technical information and drawings.

3. For relevant auxiliary equipment procured by customers, QRE will provide related technical information to meet requirement of equipment interface.

4. To execute stipulations in MOU or agreemaent signed by seller and buyer strictly.

5. To train staff from client for equipment installation, commissioning, application, maintenance as stipulated in the contract.

6. To reinforce pre-sales, mid-sales,after-sales service, to carry out "24-hour service", "service in advance", "overall process service", "lifelong service" in our manufacturing, installation,

commissioining and main-tance.

7. To meet spare parts’ requirement by customers at any time.